Description
The Storage Battery Systems SBS-2415S DC Load Bank 250V DC 0-150 Amp discharge tests and load tests stationary batteries as recommended. NERC standard PRC-005-2 requires that vented lead acid and nickel cadmium (NiCd) systems be discharge tested every six (6) years and valve regulated lead acid (VRLA) batteries every three (3) years. IEEE recommends load testing stationary flooded/vented lead acid and NiCd stationary batteries every five (5) years and VRLA batteries every 12-18 months. The SBS-2415S constant current load banks are an affordable way to perform easy and accurate IEEE450 (vented lead acid), IEEE1106 (NiCd) and IEEE1188 (VRLA) load tests.
Displays the voltage, current and Ah removed from the string during the test. Since this is a constant current load bank, the user also does not have to adjust the current during the test. These load banks come standard with multiple adjustable stop points and built-in protection to ensure that the batteries are never damaged due to over-discharge.
- 250V DC 0-150 Amp
- Perform IEEE450 (vented lead acid), IEEE1106 (NiCd) and IEEE1188 (VRLA) load tests
- Automatically discharges batteries unmanned without danger of over-discharging
- Continuously holds the current set throughout the test
- LCD screen displays real time voltage, discharge current and capacity/Ah removed
- Test parameters are adjustable during test without stopping test
- 3 adjustable stop points: End system voltage, Discharge time, Discharge capacity (Ah)
- Units can be slaved with the SBS-8400 and/or other load banks to increase amp draw
- Built-in protections: Overload protection, high voltage shutdown, high temperature shutdown, audible alarm, warning on LCD screen
- User can set: end system voltage, test time, capacity discharged